This list is valid from the following firmware version: 2.55.03.R
Measured value / Parameter | Parameter name for BLUETOOTH or Speedwire/Webconnect | Parameter name for RS485 | Read level | Displayed group in the communication product | Value range / set values | Default value | Step size | Write level | Grid Guard |
---|---|---|---|---|---|---|---|---|---|
Parameter | Fan test | CoolSys.FanTst | ![]() | Device > Cooling system > Fan test |
| Off (Off) | ‒ | ![]() | - |
Measured value | Country standard set | Cntry | ![]() | Grid Monitoring > Grid monitoring > Country standard |
| VDE-AR-N4105-MP (VDE-AR-N4105-MP) | ‒ | ‒ | - |
Parameter | Set country standard | CntrySet | ![]() | Grid Monitoring > Grid monitoring > Set country standard |
| ‒ | ‒ | ![]() | - |
Parameter | Activation of active power gradient for reconnection after grid fault | WGraReconEna | ![]() | System and device control > Inverter > Curr. active power grad., reconnection, grid fault |
| Off (Off) | ‒ | ![]() | - |
Parameter | Status of islanding detection frequency monitor | Aid.HzMonStt | ![]() | Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Frequency monitoring > Status |
| On (On) | ‒ | ![]() | - |
Parameter | Status of islanding detection unbalance detection | Aid.AsymDetStt | ![]() | Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Unbalance detection > Status |
| On (On) | ‒ | ![]() | - |
Parameter | Login required for GridGuard parameter | Login.Mdt | ![]() | Grid Monitoring > Grid monitoring > Country standard > Login prescribed |
| Yes (Yes) | ‒ | ‒ | - |
Parameter | Operating mode of dynamic grid support, dynamic grid support configuration | DGS-DGSMod | ![]() | System and device control > Inverter > Configuration of dynamic grid support > Operating mode of dynamic grid support |
| Limited dynamic grid support (DGSPa) | ‒ | ![]() | - |
Parameter | Operating mode of stat.V stab., stat.V stab. config. | Q-VArMod | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Operating mode of static voltage stabilization |
| cosPhi, direct specific. (PFCnst) | ‒ | ![]() | - |
Parameter | Excit. type at start point, cosPhi(P) char. conf. | PF-PFExtStr | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Excitation type at starting point |
| Overexcited (OvExt) | ‒ | ![]() | - |
Parameter | Excit. type at end point, cosPhi(P) char. config. | PF-PFExtStop | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Excitation type at end point |
| Underexcited (UnExt) | ‒ | ![]() | - |
Parameter | cosPhi excit.type, cosPhi config., direct spec. | PF-PFExt | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi, direct specification > Excitation type of cosPhi |
| Underexcited (UnExt) | ‒ | ![]() | - |
Parameter | Operating mode of active power reduction in case of overfrequency P(f) | P-WCtlHzMod | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Operating mode active power red., overfreq. P(f) |
| Off (Off) | ‒ | ![]() | - |
Parameter | Activation of stay-set indicator function, linear instantaneous power gradient configuration | P-HystEna | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Activation of stay-set indicator function |
| On (On) | ‒ | ![]() | - |
Parameter | Operating mode of feed-in management | P-WMod | ![]() | System and device control > Inverter > Configuration of feed-in management > Operating mode Active power |
| Act. power lim. via PV system ctrl (WCtlCom) | ‒ | ![]() | - |
Parameter | X-axes reference, conf. of grid integration char. 1 | UtilCrv1-XRef | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X-axes reference |
| Voltage in percentages of Un (XRefVNom) | ‒ | ![]() | - |
Parameter | Y-axes reference, conf. of grid integration char. 1 | UtilCrv1-YRef | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y-axes reference |
| Power in percentages of Pmax (YRefWNom) | ‒ | ![]() | - |
Parameter | Input unit, conf. of grid integration char. 2 | UtilCrv2-XRef | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X-axes reference |
| Voltage in percentages of Un (XRefVNom) | ‒ | ![]() | - |
Parameter | Output frequency, conf. of grid integration char. 2 | UtilCrv2-YRef | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y-axes reference |
| Var in percentages of Pmax (YRefVarNom) | ‒ | ![]() | - |
Parameter | Operating mode of power control module | PCM-OpMode | ![]() | System and device control > Power control module > Operating mode |
| Active power limitation (ModWMax) | ‒ | ![]() | - |
Parameter | Device class | MainModel | ![]() | Type Label > Type Label > Device class |
| Solar Inverters (DevClss1) | ‒ | ‒ | - |
Parameter | Device type | Model | ![]() | Type Label > Type Label > Device type |
| STP 5000TL-20 (STP 5000TL-20) | ‒ | ‒ | - |
Measured value | Operating status | ‒ | ![]() | Status > Operation > Operating status |
| ‒ | ‒ | ‒ | - |
Measured value | Plant mains connection | ‒ | ![]() | AC Side > Operation > Mains connection |
| ‒ | ‒ | ‒ | - |
Measured value | Grid relay/contactor | Op.GriSwStt | ![]() | Status > Operation > Grid relay status |
| Open (Opn) | ‒ | ‒ | - |
Parameter | Operating condition | Op.OpModSet | ![]() | Device > Operation > Operating condition |
| MPP (Mpp) | ‒ | ![]() | - |
Parameter | Load parameter | Op.StoFncSet | ![]() | Device > Operation > Load parameter |
| ‒ | ‒ | ![]() | - |
Parameter | Reset operating data | Op.FncSetIstl | ![]() | Device > Operation > Reset operating data |
| ‒ | ‒ | ![]() | - |
Measured value | Derating | Inv.TmpLimStt | ![]() | Status > Operation > Derating |
| not active (NoneDrt) | ‒ | ‒ | - |
Measured value | Status, device control | InvCtl.Stt | ![]() | Status > Operation > Device control > Status |
| Off (Off) | ‒ | ‒ | - |
Measured value | Status, PV system control | PlntCtl.Stt | ![]() | Status > Operation > PV system control > Status |
| Off (Off) | ‒ | ‒ | - |
Parameter | Reactive current droop, full dynamic grid support configuration | DGS-ArGraMod | ![]() | System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Reactive current droop |
| Medium-Voltage Directive (Germany) (MVtgDirective) | ‒ | ![]() | - |
Parameter | Grid disconn. at 0% specif. by feeding management | P-GriSwOpnZerW | ![]() | System and device control > Inverter > Configuration of feed-in management > Grid disconnection for 0% feeding |
| No (No) | ‒ | ![]() | - |
Parameter | Reactive power droop mode, reactive power/voltage characteristic curve configuration Q(U) | Q-VArGraMod | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Reactive power droop mode |
| Hysteresis (Hyst) | ‒ | ![]() | - |
Parameter | Excitation type that can be changed by PV system ctrl | ‒ | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > cosPhi config. method of PV system control > Excitation type of cosPhi |
| ‒ | ‒ | ![]() | - |
Parameter | Fast shut-down | ‒ | ![]() | System and device control > Inverter > Fast shut-down |
| ‒ | ‒ | ![]() | - |
Parameter | OptiTrac Global Peak switched on | MPPShdw.IsOn | ![]() | DC Side > DC settings > OptiTrac Global Peak > Activated |
| Yes (Yes) | ‒ | ![]() | - |
Parameter | RCD adjustment | ‒ | ![]() | Device > Inverter > RCD adjustment |
| Off (Off) | ‒ | ![]() | - |
Parameter | Operating mode for absent active power limitation | WCtlCom.MssMod | ![]() | System and device control > Inverter > Configuration of system control via communication > Act. power lim. via PV system ctrl > Operating mode for absent system control |
| Values maintained (UsStp) | ‒ | ![]() | - |
Parameter | Operating mode for absent reactive power control | QCtlCom.MssMod | ![]() | System and device control > Inverter > Configuration of system control via communication > Q specified by PV system control > Operating mode for absent system control |
| Values maintained (UsStp) | ‒ | ![]() | - |
Parameter | Operating mode for absent cos Phi spec | PFCtlCom.MssMod | ![]() | System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Operating mode for absent system control |
| Values maintained (UsStp) | ‒ | ![]() | - |
Parameter | Fallback stimulation type for absent cos Phi spec | PFCtlCom.FlbExt | ![]() | System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Fallback excitation type |
| Underexcited (UnExt) | ‒ | ![]() | - |
Measured value | Current spec. stimulation type cos Phi | Op.Dmd.PFExtCtl | ![]() | System and device control > Operation > Specification > Excitation type cos Phi |
| Information not available (NaNStt) | ‒ | ‒ | - |
Parameter | Maximum Bluetooth power | BtPwr | ![]() | System communication > Bluetooth > Maximum Bluetooth transmission power | 1 dBm to 20 dBm | 16 dBm | 1 | ![]() | ![]() |
Measured value | Operating condition temperatures | ‒ | ![]() | Device > Cooling system > Operating condition temperatures | ‒ | ‒ | ‒ | ‒ | - |
Measured value | DC current input | A1.Ms.Amp, A2.Ms.Amp, A3.Ms.Amp, A4.Ms.Amp, A5.Ms.Amp, B1.Ms.Amp, A.Ms.Amp, B.Ms.Amp | ![]() | DC Side > DC measurements > Current | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition DC current input | ‒ | ![]() | DC Side > DC measurements > Operating condition current | ‒ | ‒ | ‒ | ‒ | - |
Measured value | DC voltage input | A.Ms.Vol, B.Ms.Vol | ![]() | DC Side > DC measurements > Voltage | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition DC voltage input | ‒ | ![]() | DC Side > DC measurements > Operating condition voltage | ‒ | ‒ | ‒ | ‒ | - |
Measured value | DC power input | A.Ms.Watt, B.Ms.Watt | ![]() | DC Side > DC measurements > Power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition DC power input | ‒ | ![]() | DC Side > DC measurements > Operating condition power | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Start delay input | A.StrTms, B.StrTms | ![]() | DC Side > DC settings > Start delay | 1 s to 4 s | 1 s | 1 | ![]() | - |
Parameter | Minimum voltage input | A.VStr, B.VStr | ![]() | DC Side > DC settings > Critical voltage to start feed-in | 188.00 V to 800.00 V | 188.00 V | 0.01 | ![]() | - |
Parameter | Constant voltage setpoint | A.Const.VSet, B.Const.VSet | ![]() | DC Side > DC settings > Constant voltage control > Voltage setpoint | 188.00 V to 950.00 V | 950.00 V | 0.01 | ![]() | - |
Parameter | Grid nominal voltage | VRtg | ![]() | Grid Monitoring > Grid monitoring > Country standard > Nominal voltage | 100 V to 280 V | 1 | ![]() | ![]() | |
Parameter | Nominal frequency | HzRtg | ![]() | Grid Monitoring > Grid monitoring > Country standard > Nominal frequency | 44.00 Hz to 65.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Reconnection time upon restart | GriStrTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Reconnection time upon restart | 0.000 s to 1600.000 s | 0.001 | ![]() | ![]() | |
Parameter | Reconnection time upon grid interruption | GriFltMonTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Reconnection time upon grid interruption | 0.000 s to 1600.000 s | 0.001 | ![]() | ![]() | |
Parameter | Reconnection time upon short interruption | GriFltReConTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Reconnection time upon short interruption | 0.000 s to 1600.000 s | 0.001 | ![]() | ![]() | |
Parameter | Maximum duration of a short interruption | GriFltTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Maximum duration of a short interruption | 0.000 s to 400.000 s | 0.001 | ![]() | ![]() | |
Parameter | Tripping threshold DC current monitoring | AMaxOfs | ![]() | Grid Monitoring > Grid monitoring > Country standard > Tripping threshold DC current monitoring | 0.020 A to 2.000 A | 0.001 | ![]() | ![]() | |
Parameter | Tripping time DC current monitoring | AMaxOfsTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Tripping time DC current monitoring | 0 ms to 10000 ms | 1 | ![]() | ![]() | |
Parameter | Minimum insulation resistance | Iso.LeakRisMin | ![]() | Grid Monitoring > Grid monitoring > Country standard > Minimum insulation resistance | 100000 Ω to 3000000 Ω | 1 | ![]() | ![]() | |
Parameter | Active power gradient connection | WGraConn | ![]() | System and device control > Inverter > Active power gradient connection | 1 % to 10000 % | 1 | ![]() | ![]() | |
Parameter | Reconnect gradient after grid fault | WGraRecon | ![]() | System and device control > Inverter > Power gradient for reconnection after grid fault | 2 % to 10000 % | 1 | ![]() | ![]() | |
Parameter | Tripping time of islanding detection frq. monitor | Aid.HzMonTmms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Frequency monitoring > Tripping time of the frequency monitor | 0 ms to 10000 ms | 1 | ![]() | ![]() | |
Parameter | Permissible grid unbalance of islanding detection | Aid.AsymDetMax | ![]() | Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Unbalance detection > Permissible grid unbalance | 0 % to 50 % | 1 | ![]() | ![]() | |
Parameter | Trip.time of islanding detection unbalance detect. | Aid.AsymDetMaxT | ![]() | Grid Monitoring > Grid monitoring > Country standard > Islanding detection > Unbalance detection > Tripping time of the unbalance detection | 0 ms to 10000 ms | 1 | ![]() | ![]() | |
Parameter | Voltage monitoring upper maximum threshold | VolCtl.Max | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper maximum threshold | 300.00 V to 420.00 V | 0.01 | ![]() | ![]() | |
Parameter | Voltage monitoring upper max. threshold trip. time | VolCtl.MaxTmms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper maximum threshold tripping time | 0.100 ms to 5.000 ms | 0.312 ms | 0.001 | ![]() | ![]() |
Parameter | Voltage monitoring median maximum threshold | VolCtl.hhLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median maximum threshold | 100.00 V to 300.00 V | 0.01 | ![]() | ![]() | |
Parameter | Voltage monitoring median max. threshold trip.time | VolCtl.hhLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median maximum threshold tripping time | 0 ms to 60000 ms | 1 | ![]() | ![]() | |
Parameter | Voltage monitoring lower maximum threshold | VolCtl.hLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower maximum threshold | 100.00 V to 280.00 V | 0.01 | ![]() | ![]() | |
Parameter | Voltage monitoring lower max. threshold trip. time | VolCtl.hLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower maximum threshold tripping time | 0 ms to 60000 ms | 1 | ![]() | ![]() | |
Parameter | Voltage monitoring lower minimum threshold | VolCtl.lLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper minimum threshold | 45.00 V to 230.00 V | 0.01 | ![]() | ![]() | |
Parameter | Voltage monitoring lower min. threshold trip. time | VolCtl.lLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper minimum threshold tripping time | 0 ms to 10000 ms | 1 | ![]() | ![]() | |
Parameter | Voltage monitoring of median minimum threshold | VolCtl.llLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median minimum threshold | 45.00 V to 230.00 V | 0.01 | ![]() | ![]() | |
Parameter | Voltage monitoring median min. threshold trip.time | VolCtl.llLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Median minimum threshold tripping time | 0 ms to 10000 ms | 1 | ![]() | ![]() | |
Parameter | Voltage increase protection | VolCtl.Rpro | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Voltage increase protection | 100.00 V to 280.00 V | 0.01 | ![]() | ![]() | |
Parameter | Min. voltage for reconnection | VolCtl.ReconMin | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Lower reconnection limit | 45.00 V to 240.00 V | 0.01 | ![]() | ![]() | |
Parameter | Max. voltage for reconnection | VolCtl.ReconMax | ![]() | Grid Monitoring > Grid monitoring > Country standard > Voltage monitoring > Upper limit for reconnection | 100.00 V to 280.00 V | 0.01 | ![]() | ![]() | |
Parameter | Frequency monitoring median maximum threshold | FrqCtl.hhLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median maximum threshold | 50.00 Hz to 65.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Frq. monitoring median max. threshold trip. time | FrqCtl.hhLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median maximum threshold tripping time | 0 ms to 10000 ms | 1 | ![]() | ![]() | |
Parameter | Frequency monitoring lower maximum threshold | FrqCtl.hLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower maximum threshold | 50.00 Hz to 65.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Frq. monitoring lower max. threshold trip. time | FrqCtl.hLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower maximum threshold tripping time | 0 ms to 90000 ms | 1 | ![]() | ![]() | |
Parameter | Frequency monitoring upper minimum threshold | FrqCtl.lLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper minimum threshold | 44.00 Hz to 60.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Frq. monitoring upper min. threshold trip. time | FrqCtl.lLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper minimum threshold tripping time | 0 ms to 300000 ms | 1 | ![]() | ![]() | |
Parameter | Frequency monitoring median minimum threshold | FrqCtl.llLim | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median minimum threshold | 44.00 Hz to 60.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Frq. monitoring median min. threshold trip. time | FrqCtl.llLimTms | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Median minimum threshold tripping time | 0 ms to 300000 ms | 1 | ![]() | ![]() | |
Parameter | Maximum allowable frequency drift | FrqCtl.ChgMax | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Max. frequency change per second | 0.00 Hz to 10.00 Hz | 10.00 Hz | 0.01 | ![]() | ![]() |
Parameter | Tripping time when exceeding max. frequency drift | FrqCtl.ChgMaxTm | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Tripping time for max. frequency change per second | 0 ms to 10000 ms | 10,000 ms | 1 | ![]() | ![]() |
Parameter | Lower frequency for reconnection | FrqCtl.ReconMin | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Lower reconnection limit | 44.00 Hz to 60.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Upper frequency for reconnection | FrqCtl.ReconMax | ![]() | Grid Monitoring > Grid monitoring > Country standard > Frequency monitoring > Upper limit for reconnection | 50.00 Hz to 65.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Hysteresis voltage, dynamic grid support configuration | DGS-HystVolNom | ![]() | System and device control > Inverter > Configuration of dynamic grid support > Hysteresis voltage | 0 % to 100 % | 5 % | 1 | ![]() | ![]() |
Parameter | PWM inverse voltage, dynamic grid support configuration | DGS-PWMVolNom | ![]() | System and device control > Inverter > Configuration of dynamic grid support > PWM inverse voltage at undervoltage | 0 % to 100 % | 1 | ![]() | ![]() | |
Parameter | cosPhi at start point, cosPhi(P) char. config. | PF-PFStr | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > cosPhi of start point | 0.80 to 1.00 | 1.00 | 0.01 | ![]() | ![]() |
Parameter | Act. power at start point, cosPhi(P) char. config. | PF-WNomStr | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Active power at starting point | 0 % to 100 % | 1 | ![]() | ![]() | |
Parameter | cosPhi at end point, cosPhi(P) char. config. | PF-PFStop | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > cosPhi of end point | 0.80 to 1.00 | 0.01 | ![]() | ![]() | |
Parameter | Act. power at end point, cosPhi(P) char. config. | PF-WNomStop | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Active power at end point | 0 % to 100 % | 100 % | 1 | ![]() | ![]() |
Parameter | Activating voltage, cosPhi(P) char. conf. | PF-EnaVol | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Activating voltage | 0.0 % to 120.0 % | 0.1 | ![]() | ![]() | |
Parameter | Deactivating voltage, cosPhi(P) char. conf. | PF-DsaVol | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi(P) characteristic > Deactivating voltage | 0.0 % to 120.0 % | 0.1 | ![]() | ![]() | |
Parameter | cosPhi setpoint, cosPhi config., direct specif. | PF-PF | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Configuration of cosPhi, direct specification > cosPhi specification | 0.80 to 1.00 | 0.01 | ![]() | ![]() | |
Parameter | Waiting time of active power grad. after reset frequency, conf. of linear instantaneous power gradient | P-HzStopWGraTms | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Min. time until activation of active power gradient after reset frequency | 0 s to 1600 s | 1 | ![]() | ![]() | |
Parameter | Lower frequency limit prior to end of active power reduction, linear instant. power gradient conf. | P-HzStopMin | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Lower frequency deviation limit prior to active power release | −5.00 Hz to 0.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Upper frequency limit prior to end of active power reduction, linear instant. power gradient conf. | P-HzStopMax | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Upper frequency deviation limit prior to active power release | 0.00 Hz to 5.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Active power gradient after reset frequency, linear instantaneous power gradient configuration | P-HzStopWGra | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Active power gradient after reset frequency | 2 % to 10000 % | 1 | ![]() | ![]() | |
Parameter | Difference between starting frequency and grid frequency, linear instantaneous power gradient configuration | P-HzStr | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Difference between starting freq. and grid freq. | 0.00 Hz to 5.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Difference between reset frequency and grid frequency, linear instantaneous power gradient configuration | P-HzStop | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Difference between reset frequency and grid freq. | 0.00 Hz to 5.00 Hz | 0.01 | ![]() | ![]() | |
Parameter | Active power gradient, linear instantaneous power gradient configuration | P-WGra | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Active power gradient | 10 % to 130 % | 1 | ![]() | ![]() | |
Parameter | Tripping time for active power limitation | P-WCtlTmms | ![]() | System and device control > Inverter > Config. active power reduct. at overfrequency P(f) > Config. of linear instantaneous power gradient > Tripping time for active power limitation | 0 ms to 60000 ms | 0 ms | 1 | ![]() | ![]() |
Parameter | Characteristic curve number of the PV system control procedure P(U) | P-WCtlVolCrvNum | ![]() | System and device control > Inverter > Conf. of the PV system control procedure P(U) > Characteristic curve number | 0 to 2 | 1 | ![]() | ![]() | |
Parameter | Number of points to be used, conf. of grid integr. char. 1 | UtilCrv1-NumPt | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Number of points to be used | 1 to 8 | 2 | 1 | ![]() | ![]() |
Parameter | X value 1, conf. of grid integr. char. 1 | UtilCrv1-XVal1 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 1 | 70.000 to 280.000 | 0.001 | ![]() | ![]() | |
Parameter | Y value 1, conf. of grid integr. char. 1 | UtilCrv1-YVal1 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 1 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 2, conf. of grid integr. char. 1 | UtilCrv1-XVal2 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 2 | 70.000 to 280.000 | 0.001 | ![]() | ![]() | |
Parameter | Y value 2, conf. of grid integr. char. 1 | UtilCrv1-YVal2 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 2 | −100.000 to +100.000 | 0.001 | ![]() | ![]() | |
Parameter | X value 3, conf. of grid integr. char. 1 | UtilCrv1-XVal3 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 3 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 3, conf. of grid integr. char. 1 | UtilCrv1-YVal3 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 3 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 4, conf. of grid integr. char. 1 | UtilCrv1-XVal4 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 4 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 4, conf. of grid integr. char. 1 | UtilCrv1-YVal4 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 4 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 5, conf. of grid integr. char. 1 | UtilCrv1-XVal5 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 5 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 5, conf. of grid integr. char. 1 | UtilCrv1-YVal5 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 5 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 6, conf. of grid integr. char. 1 | UtilCrv1-XVal6 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 6 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 6, conf. of grid integr. char. 1 | UtilCrv1-YVal6 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 6 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 7, conf. of grid integr. char. 1 | UtilCrv1-XVal7 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 7 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 7, conf. of grid integr. char. 1 | UtilCrv1-YVal7 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 7 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 8, conf. of grid integr. char. 1 | UtilCrv1-XVal8 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > X value 8 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 8, conf. of grid integr. char. 1 | UtilCrv1-YVal8 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Y value 8 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Adjustment time of characteristic operating point, conf. of grid integr. char. 1 | UtilCrv1-CrvTms | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Adjustm. time characteristic curve operating point | 0.0 s to 1000.0 s | 10.0 s | 0.1 | ![]() | ![]() |
Parameter | Decrease ramp, conf. of grid integr. char. 1 | UtilCrv1-RmpDec | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Decrease ramp | 1.0 % to 10000.0 % | 1,200.0 % | 0.1 | ![]() | ![]() |
Parameter | Increase ramp, conf. of grid integr. char. 1 | UtilCrv1-RmpInc | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 1 > Increase ramp | 1.0 % to 10000.0 % | 1,200.0 % | 0.1 | ![]() | ![]() |
Parameter | Characteristic number, conf. of reactive power/voltage char. Q(U) | Q-VArCtlVCrvNum | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Conf. of reactive power/volt. char. Q(U) with meas. points > Characteristic curve number | 0 to 2 | 1 | ![]() | ![]() | |
Parameter | Activating active power, conf. of reactive power/voltage char. Q(U) | Q-EnaW | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Conf. of reactive power/volt. char. Q(U) with meas. points > Activating active power | 0 % to 100 % | 1 | ![]() | ![]() | |
Parameter | Deactivating active power, conf. of reactive power/voltage char. Q(U) | Q-DsaW | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Conf. of reactive power/volt. char. Q(U) with meas. points > Deactivating active power | 0 % to 100 % | 1 | ![]() | ![]() | |
Parameter | Number of points to be used, conf. of grid integr. char. 2 | UtilCrv2-NumPt | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Number of points to be used | 1 to 8 | 4 | 1 | ![]() | ![]() |
Parameter | X value 1, conf. of grid integr. char. 2 | UtilCrv2-XVal1 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 1 | 70.000 to 280.000 | 0.001 | ![]() | ![]() | |
Parameter | Y value 1, conf. of grid integr. char. 2 | UtilCrv2-YVal1 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 1 | −100.000 to +100.000 | 0.001 | ![]() | ![]() | |
Parameter | X value 2, conf. of grid integr. char. 2 | UtilCrv2-XVal2 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 2 | 70.000 to 280.000 | 0.001 | ![]() | ![]() | |
Parameter | Y value 2, conf. of grid integr. char. 2 | UtilCrv2-YVal2 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 2 | −100.000 to +100.000 | 0.001 | ![]() | ![]() | |
Parameter | X value 3, conf. of grid integr. char. 2 | UtilCrv2-XVal3 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 3 | 70.000 to 280.000 | 0.001 | ![]() | ![]() | |
Parameter | Y value 3, conf. of grid integr. char. 2 | UtilCrv2-YVal3 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 3 | −100.000 to +100.000 | 0.001 | ![]() | ![]() | |
Parameter | X value 4, conf. of grid integr. char. 2 | UtilCrv2-XVal4 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 4 | 70.000 to 280.000 | 0.001 | ![]() | ![]() | |
Parameter | Y value 4, conf. of grid integr. char. 2 | UtilCrv2-YVal4 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 4 | −100.000 to +100.000 | 0.001 | ![]() | ![]() | |
Parameter | X value 5, conf. of grid integr. char. 2 | UtilCrv2-XVal5 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 5 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 5, conf. of grid integr. char. 2 | UtilCrv2-YVal5 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 5 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 6, conf. of grid integr. char. 2 | UtilCrv2-XVal6 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 6 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 6, conf. of grid integr. char. 2 | UtilCrv2-YVal6 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 6 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 7, conf. of grid integr. char. 2 | UtilCrv2-XVal7 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 7 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 7, conf. of grid integr. char. 2 | UtilCrv2-YVal7 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 7 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | X value 8, conf. of grid integr. char. 2 | UtilCrv2-XVal8 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > X value 8 | 70.000 to 280.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Y value 8, conf. of grid integr. char. 2 | UtilCrv2-YVal8 | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Y value 8 | −100.000 to +100.000 | 100.000 | 0.001 | ![]() | ![]() |
Parameter | Adjustment time of char. operating point, conf. of grid integration char. 2 | UtilCrv2-CrvTms | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Adjustm. time characteristic curve operating point | 0.0 s to 1000.0 s | 0.1 | ![]() | ![]() | |
Parameter | Tripping time for activation of char. curve 2 | UtilCrv2-ActTms | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Tripping time | 0 s to 1000 s | 1 | ![]() | ![]() | |
Parameter | Decrease ramp, conf. of grid integration char. 2 | UtilCrv2-RmpDec | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Decrease ramp | 1.0 % to 10000.0 % | 0.1 | ![]() | ![]() | |
Parameter | Increase ramp, conf. of grid integration char. 2 | UtilCrv2-RmpInc | ![]() | System and device control > Inverter > Conf. of the grid integr. characteristic curves > Characteristic 2 > Increase ramp | 1.0 % to 10000.0 % | 0.1 | ![]() | ![]() | |
Parameter | Reference voltage, PV system control | VRef | ![]() | AC Side > Inverter > PV system control > Reference voltage | 80 V to 245 V | 1 | ![]() | ![]() | |
Parameter | Reference correction voltage, PV system control | VRefOfs | ![]() | AC Side > Inverter > PV system control > Reference correction voltage | −20 V to +20 V | 0 V | 1 | ![]() | ![]() |
Measured value | Grid frequency | GridMs.Hz | ![]() | AC Side > Grid measurements > Grid frequency | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition grid frequency | ‒ | ![]() | AC Side > Grid measurements > Operating condition grid frequency | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Apparent power | GridMs.TotVA | ![]() | AC Side > Grid measurements > Apparent power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Normalized total apparent power | ‒ | ![]() | AC Side > Grid measurements > Normalized total apparent power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Apparent power L1 | GridMs.VA.phsA | ![]() | AC Side > Grid measurements > Apparent power > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Apparent power L2 | GridMs.VA.phsB | ![]() | AC Side > Grid measurements > Apparent power > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Apparent power L3 | GridMs.VA.phsC | ![]() | AC Side > Grid measurements > Apparent power > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Reactive power | GridMs.TotVAr | ![]() | AC Side > Grid measurements > Reactive power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition reactive power | ‒ | ![]() | AC Side > Grid measurements > Operating condition reactive power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Reactive power L1 | GridMs.VAr.phsA | ![]() | AC Side > Grid measurements > Reactive power > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Reactive power L2 | GridMs.VAr.phsB | ![]() | AC Side > Grid measurements > Reactive power > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Reactive power L3 | GridMs.VAr.phsC | ![]() | AC Side > Grid measurements > Reactive power > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Displacement power factor | GridMs.TotPF | ![]() | AC Side > Grid measurements > Displacement power factor | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Power | Pac | ![]() | AC Side > Grid measurements > Power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition power | ‒ | ![]() | AC Side > Grid measurements > Operating condition power | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Power L1 | GridMs.W.phsA | ![]() | AC Side > Grid measurements > Power per phase > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Power L2 | GridMs.W.phsB | ![]() | AC Side > Grid measurements > Power per phase > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Power L3 | GridMs.W.phsC | ![]() | AC Side > Grid measurements > Power per phase > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid current phase L1 | GridMs.A.phsA | ![]() | AC Side > Grid measurements > Phase currents > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition current L1 | ‒ | ![]() | AC Side > Grid measurements > Operating condition current > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid current phase L2 | GridMs.A.phsB | ![]() | AC Side > Grid measurements > Phase currents > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition current L2 | ‒ | ![]() | AC Side > Grid measurements > Operating condition current > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid current phase L3 | GridMs.A.phsC | ![]() | AC Side > Grid measurements > Phase currents > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition current L3 | ‒ | ![]() | AC Side > Grid measurements > Operating condition current > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid current | ‒ | ![]() | AC Side > Grid measurements > Phase total Current | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid voltage phase L1 | GridMs.PhV.phsA | ![]() | AC Side > Grid measurements > Phase voltage > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition grid voltage L1 | ‒ | ![]() | AC Side > Grid measurements > Operating condition voltage > Phase L1 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid voltage phase L2 | GridMs.PhV.phsB | ![]() | AC Side > Grid measurements > Phase voltage > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition grid voltage L2 | ‒ | ![]() | AC Side > Grid measurements > Operating condition voltage > Phase L2 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Grid voltage phase L3 | GridMs.PhV.phsC | ![]() | AC Side > Grid measurements > Phase voltage > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition grid voltage L3 | ‒ | ![]() | AC Side > Grid measurements > Operating condition voltage > Phase L3 | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Maximum active power device | Plimit | ![]() | Device > Inverter > Maximum active power | 1 | ‒ | - | ||
Parameter | Set active power limit | Pmax | ![]() | Device > Inverter > Currently set active power limit | 1 | ![]() | - | ||
Parameter | Active power gradient | WGra | ![]() | System and device control > Inverter > Active power gradient | 1 % to 1000 % | 20 % | 1 | ![]() | ![]() |
Parameter | Deactivation delay | Inv.StopTms | ![]() | Device > Inverter > Deactivation delay | 1 s to 3600 s | 2 s | 1 | ![]() | - |
Parameter | End point of the power control via frequency | OffGri.HzdLim | ![]() | AC Side > Inverter > Island mode > End point of the power control via frequency | 0.00 Hz to 5.00 Hz | 2.00 Hz | 0.01 | ![]() | - |
Parameter | Start. point of the power control via frequency | OffGri.HzdStr | ![]() | AC Side > Inverter > Island mode > Start point of the power control via frequency | 0.00 Hz to 5.00 Hz | 1.00 Hz | 0.01 | ![]() | - |
Parameter | Currently set apparent power limit | Smax | ![]() | Device > Inverter > Currently set apparent power limit | 1 | ![]() | - | ||
Parameter | Maximum apparent power device | Slimit | ![]() | Device > Inverter > Maximum apparent power | 1 | ‒ | - | ||
Parameter | Reactive power gradient | VArGra | ![]() | System and device control > Inverter > Reactive power gradient | 1 % to 50 % | 20 % | 1 | ![]() | ![]() |
Measured value | Residual current | Iso.FltA | ![]() | DC Side > Insulation monitoring > Residual current | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition residual current | ‒ | ![]() | DC Side > Insulation monitoring > Operating condition residual current | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Insulation resistance | Riso | ![]() | DC Side > Insulation monitoring > Insulation resistance | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating condition insulation resistance | ‒ | ![]() | DC Side > Insulation monitoring > Operating condition insulation resistance | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Operating time | Mt.TotTmh | ![]() | AC Side > Measured values > Operating time | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Set total operating time at grid connection point | Mt.TotTmhSet | ![]() | AC Side > Measured values > Set operating time | 0 h to 440000 h | 0 h | 1 | ![]() | - |
Measured value | Feed-in time | Mt.TotOpTmh | ![]() | AC Side > Measured values > Feed-in time | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Set total feed-in time at the grid connection pt. | Mt.TotOpTmhSet | ![]() | AC Side > Measured values > Set feed-in time | 0 h to 440000 h | 0 h | 1 | ![]() | - |
Measured value | Total yield | E-Total | ![]() | AC Side > Measured values > Total yield | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Set total yield | Mt.TotkWhSet | ![]() | AC Side > Measured values > Set total yield | 0 kWh to 4000000 kWh | 0 kWh | 1 | ![]() | - |
Parameter | Communication version | ComRev | ![]() | Type Label > Type Label > Communication version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Serial number | SerNumSet, Serial Number | ![]() | Type Label > Type Label > Serial number | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Firmware version of the main processor | HP.swRev | ![]() | Device Components > Type Label > Main processor > Software version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Hardware version of the main processor | HP.hwRev | ![]() | Device Components > Type Label > Main processor > Hardware version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Revision status of the main processor | HP.RevVer | ![]() | Device Components > Type Label > Main processor > Revision status | 0 to 255 | 0 | 1 | ‒ | - |
Parameter | Serial number of the main processor | CmpMain.SerNum | ![]() | Device Components > Type Label > Main processor > Serial number | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | SUSyID of the main processor | CmpMain.SusyId | ![]() | Device Components > Type Label > Main processor > SUSyID | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Firmware version of the logic component | CPLD.swRev | ![]() | Device Components > Type Label > Logic component > Software version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Revision status of the logic component | CPLD.RevVer | ![]() | Device Components > Type Label > Logic component > Revision status | 0 to 255 | 0 | 1 | ‒ | - |
Measured value | Number of grid connections | Op.GriSwCnt | ![]() | AC Side > Operation > N° grid conn. at grid conn.pt. | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Active power limitation P, active power configuration | P-W | ![]() | System and device control > Inverter > Configuration of feed-in management > Configuration of active power P limitation > Power per phase | 1 | ![]() | ![]() | ||
Parameter | Active power limitation P, active power configuration | P-WNom | ![]() | System and device control > Inverter > Configuration of feed-in management > Configuration of active power P limitation > Power per phase | 0 % to 100 % | 100 % | 1 | ![]() | ![]() |
Parameter | Reactive power set value as a % | Q-VArNom | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. of reactive power Q, direct specification > Reactive power setpoint Q | −60.0 % to +60.0 % | 0.0 % | 0.1 | ![]() | ![]() |
Parameter | Specified voltage UQ0, reactive power/voltage characteristic curve configuration Q(U) | Q-VolRefNom | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Specified voltage UQ0 | 80 % to 120 % | 100 % | 1 | ![]() | ![]() |
Parameter | Symmetrical limit for maximum reactive power, reactive power/voltage characteristic curve configuration Q(U) | Q-VArMaxNom | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Symmetrical limit for maximum reactive power | 0.0 % to 60.0 % | 0.0 % | 0.1 | ![]() | ![]() |
Parameter | Voltage spread, reactive power/voltage characteristic curve configuration Q(U) | Q-VolWidNom | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Voltage spread | 0.0 % to 20.0 % | 0.0 % | 0.1 | ![]() | ![]() |
Parameter | Reactive power gradient, reactive power/voltage characteristic curve configuration Q(U) | Q-VArGraNom | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Reactive power gradient | 0.0 % to 10.0 % | 0.0 % | 0.1 | ![]() | ![]() |
Parameter | Adjustment time for characteristic operating point, reactive power/voltage characteristic curve configuration Q(U) | Q-VArTms | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power/voltage charact. curve Q(U) > Adjustment time for charact. curve operating point | 2 s to 60 s | 10 s | 1 | ![]() | ![]() |
Parameter | PWM inversion delay, dynamic grid support configuration | DGS-PWMTms | ![]() | System and device control > Inverter > Configuration of dynamic grid support > PWM inversion delay at undervoltage | 0.00 s to 5.00 s | 0.00 s | 0.01 | ![]() | ![]() |
Parameter | Gradient K of the reactive current droop, full dynamic grid support configuration | DGS-ArGraNomPrc | ![]() | System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Gradient K of the reactive current droop | 0.00 % to 10.00 % | 2.30 % | 0.01 | ![]() | ![]() |
Parameter | Lower limit, voltage dead band, full dynamic grid support configuration | DGS-DbVolNomMin | ![]() | System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Lower limit, voltage dead band | −40 % to 0 % | −10 % | 1 | ![]() | ![]() |
Parameter | Upper limit, voltage dead band, full dynamic support configuration | DGS-DbVolNomMax | ![]() | System and device control > Inverter > Configuration of dynamic grid support > Configuration of full dynamic grid support > Upper limit, voltage dead band | 0 % to 40 % | 10 % | 1 | ![]() | ![]() |
Parameter | Normalized reactive power limitation by PV system ctrl | ‒ | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power mode of PV system control > Reactive power setpoint Q | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Normalized reactive power limitation by PV system ctrl | ‒ | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > Config. reactive power mode of PV system control > Reactive power setpoint Q | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Active power limitation by PV system control | ‒ | ![]() | System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Power per phase | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Normalized active power limitation by PV system ctrl | ‒ | ![]() | System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Power per phase | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Normalized active power limitation by PV system ctrl | ‒ | ![]() | System and device control > Inverter > Configuration of feed-in management > Configuration of active power mode of PV system ctrl > Power per phase | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Dis.pow.factor that can be changed via PV system ctrl | ‒ | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > cosPhi config. method of PV system control > cosPhi specification | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Setpoint cos(phi) as per EEI convention | ‒ | ![]() | System and device control > Inverter > Configuration of static voltage stabilization > cosPhi config. method of PV system control > Setpoint cos(phi) as per EEI | ‒ | ‒ | ‒ | ![]() | - |
Parameter | Cycle time of the OptiTrac Global Peak algorithm | MPPShdw.CycTms | ![]() | DC Side > DC settings > OptiTrac Global Peak > Cycle time | 360 s to 1800 s | 360 s | 1 | ![]() | - |
Parameter | Timeout for absent active power limitation | WCtlCom.TmsOut | ![]() | System and device control > Inverter > Configuration of system control via communication > Act. power lim. via PV system ctrl > Timeout | 5 s to 86400 s | 600 s | 1 | ![]() | - |
Parameter | Fallback act power lmt P in % of WMax for absent act power lmt | WCtlCom.FlbNom | ![]() | System and device control > Inverter > Configuration of system control via communication > Act. power lim. via PV system ctrl > Fallback active power P | 0.00 % to 100.00 % | 100.00 % | 0.01 | ![]() | - |
Parameter | Timeout for absent reactive power control | QCtlCom.TmsOut | ![]() | System and device control > Inverter > Configuration of system control via communication > Q specified by PV system control > Timeout | 5 s to 86400 s | 600 s | 1 | ![]() | - |
Parameter | Fallback react power Q in % of WMax for absent react power ctr | QCtlCom.FlbNom | ![]() | System and device control > Inverter > Configuration of system control via communication > Q specified by PV system control > Fallback reactive power Q | −60.00 % to +60.00 % | 0.00 % | 0.01 | ![]() | - |
Parameter | Timeout for absent cos Phi spec | PFCtlCom.TmsOut | ![]() | System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Timeout | 5 s to 86400 s | 600 s | 1 | ![]() | - |
Parameter | Fallback cos Phi for absent cos Phi spec | PFCtlCom.Flb | ![]() | System and device control > Inverter > Configuration of system control via communication > cosPhi, specified by PV system control > Fallback cos Phi | 0.8000 to 1.0000 | 1.0000 | 0.0001 | ![]() | - |
Measured value | Current spec. active power limitation P | Op.Dmd.WCtl | ![]() | System and device control > Operation > Specification > Active power limitation P | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Current spec. reactive power Q | Op.Dmd.VArCtl | ![]() | System and device control > Operation > Specification > Reactive power Q | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Current spec. cos Phi | Op.Dmd.PFCtl | ![]() | System and device control > Operation > Specification > cos Phi | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Ripple control signal detection, amplification of narrow-band support | RplDet-NBS-Gain | ![]() | Device > Inverter > Ripple control signal detection > Narrow-band support > Amplification | −1000.00 V/A to +1000.00 V/A | 0.00 V/A | 0.01 | ![]() | - |
Parameter | Ripple control signal detection, damping of narrow-band support | RplDet-NBS-Damp | ![]() | Device > Inverter > Ripple control signal detection > Narrow-band support > Damping | −10.00 to +10.00 | 0.10 | 0.01 | ![]() | - |
Parameter | Ripple control signal detection, frequency of narrow-band support | RplDet-NBS-Hz | ![]() | Device > Inverter > Ripple control signal detection > Narrow-band support > Grid frequency | 100.0 Hz to 2000.0 Hz | 1,000.0 Hz | 0.1 | ![]() | - |
Parameter | Type of module in module slot | Mdl.Typ | ![]() | Device Components > Type Label > Module shaft 1 > Type |
| ------- (None) | ‒ | ‒ | - |
Measured value | Condition | Op.Health | ![]() | Status > Operation > Condition |
| Off (Off) | ‒ | ‒ | - |
Measured value | Recommended action | Op.Prio | ![]() | Status > Operation > Current event > Recommended action |
| invalid (PrioIna) | ‒ | ‒ | - |
Measured value | Message | ‒ | ![]() | Status > Operation > Current event > Message |
| ‒ | ‒ | ‒ | - |
Measured value | Fault correction measure | ‒ | ![]() | Status > Operation > Current event > Fault correction measure |
| ‒ | ‒ | ‒ | - |
Parameter | Find device | ‒ | ![]() | Device > System > Find device |
| Off (Off) | ‒ | ![]() | - |
Parameter | Operating mode of multifunction relay | Mlt.OpMode | ![]() | Device > Multifunction relay > Operating mode |
| Fault indication (FltInd) | ‒ | ![]() | - |
Parameter | Status of MFR with control via communication | Mlt.ComCtl.Sw | ![]() | Device > Multifunction relay > Control via communication > Status |
| Off (Off) | ‒ | ![]() | - |
Parameter | Update operating mode | Upd.OpMode | ![]() | Device > Update > Operating mode |
| On (On) | ‒ | ![]() | - |
Parameter | Language of the user interface | CntrySet.Lang | ![]() | Device > Country settings > Language |
| English (LangEN) | ‒ | ![]() | - |
Measured value | Speedwire connection status of SMACOM A | ‒ | ![]() | System communication > Speedwire > SMACOM A > Status |
| No connection (NotConn) | ‒ | ‒ | - |
Measured value | Connection speed of SMACOM A | ‒ | ![]() | System communication > Speedwire > SMACOM A > Connection speed |
| ------- (None) | ‒ | ‒ | - |
Measured value | Duplex mode of SMACOM A | ‒ | ![]() | System communication > Speedwire > SMACOM A > Duplex mode |
| ------- (None) | ‒ | ‒ | - |
Measured value | Status of the Webconnect functionality | ‒ | ![]() | External Communication > Webconnect > Status |
| Off (Off) | ‒ | ‒ | - |
Parameter | Webconnect functionality switched on | WebConn.IsOn | ![]() | External Communication > Webconnect > Activated |
| Yes (Yes) | ‒ | ![]() | - |
Parameter | Automatic speedwire configureation switched on | ‒ | ![]() | System communication > Speedwire > Automatic configuration switched on |
| Yes (Yes) | ‒ | ![]() | - |
Measured value | Status of digital inputs of power control module | PCM-DigInStt | ![]() | System and device control > Power control module > Status of digital inputs |
| D1: 0 | D2: 0 | D3: 0 | D4: 0 (DigInD00) | ‒ | ‒ | - |
Parameter | ‒ | ‒ | ![]() | Further Applications > Operation > Active special functionality |
| ‒ (CndRemUpd) | ‒ | ‒ | - |
Parameter | Modbus TCP server on | ‒ | ![]() | External Communication > Modbus > TCP server > Activated |
| No (No) | ‒ | ![]() | - |
Parameter | Modbus UDP server on | ‒ | ![]() | External Communication > Modbus > UDP server > Activated |
| No (No) | ‒ | ![]() | - |
Parameter | Firmware version of the communication assembly | KP.swRev | ![]() | Device Components > Type Label > Communication assembly > Software version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Hardware version of the communication assembly | KP.hwRev | ![]() | Device Components > Type Label > Communication assembly > Hardware version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Revision status of the communication assembly | KP.RevVer | ![]() | Device Components > Type Label > Communication assembly > Revision status | 0 to 255 | 0 | 1 | ‒ | - |
Parameter | Serial number of the communication assembly | ‒ | ![]() | Device Components > Type Label > Communication assembly > Serial number | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | SUSyID of the communication assembly | ‒ | ![]() | Device Components > Type Label > Communication assembly > SUSyID | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Firmware version of the Bluetooth component | BT.swRev | ![]() | Device Components > Type Label > Bluetooth component > Software version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Revision status of the Bluetooth component | BT.RevVer | ![]() | Device Components > Type Label > Bluetooth component > Revision status | 0 to 255 | 0 | 1 | ‒ | - |
Parameter | Serial number of the Bluetooth component | ‒ | ![]() | Device Components > Type Label > Bluetooth component > Serial number | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | SUSyID of the Bluetooth component | ‒ | ![]() | Device Components > Type Label > Bluetooth component > SUSyID | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Revision status of the display | LCD.RevVer | ![]() | Device Components > Type Label > Display > Revision status | 0 to 255 | 0 | 1 | ‒ | - |
Parameter | Firmware version of the module | Mdl.swRev | ![]() | Device Components > Type Label > Module shaft 1 > Software version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Hardware version of the module | Mdl.hwRev | ![]() | Device Components > Type Label > Module shaft 1 > Hardware version | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | Revision status of the module | Mdl.RevVer | ![]() | Device Components > Type Label > Module shaft 1 > Revision status | 0 to 255 | 0 | 1 | ‒ | - |
Parameter | Serial number of the module | ‒ | ![]() | Device Components > Type Label > Module shaft 1 > Serial number | 0 to 4294967294 | 0 | 1 | ‒ | - |
Parameter | SUSyID of the module | ‒ | ![]() | Device Components > Type Label > Module shaft 1 > SUSyID | 0 to 4294967294 | 0 | 1 | ‒ | - |
Measured value | Waiting time until feed-in | Op.TmsRmg | ![]() | Status > Operation > Waiting time until feed-in | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Nominal power in Ok Mode | ‒ | ![]() | Status > Operation > Device status > Ok | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Nominal power in Warning Mode | ‒ | ![]() | Status > Operation > Device status > Warning | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Nominal power in Fault Mode | ‒ | ![]() | Status > Operation > Device status > Fault | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Number of events for user | Op.EvtCntUsr | ![]() | Status > Operation > Events for user | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Number of events for installer | Op.EvtCntIstl | ![]() | Status > Operation > Events for installer | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Current event number | Op.EvtNo | ![]() | Status > Operation > Current event > Current event number | ‒ | ‒ | ‒ | ‒ | - |
Measured value | Current event number for manufacturer | Op.EvtNoDvlp | ![]() | Status > Operation > Current event > Event number manufacturer | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Software package | Pkg.swRev | ![]() | Type Label > Type Label > Software package | 0 to 4294967294 | 0 | 1 | ‒ | - |
Measured value | Daily yield | ‒ | ![]() | AC Side > Measured values > Daily yield | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Minimum On time for MFR self-consumption | Mlt.MinOnTmm | ![]() | Device > Multifunction relay > Self-consumption > Minimum On time | 1 min to 1440 min | 120 min | 1 | ![]() | - |
Parameter | Minimum On power for MFR self-consumption | Mlt.MinOnPwr | ![]() | Device > Multifunction relay > Self-consumption > Minimum On power | 100 W to 12000 W | 1,500 W | 1 | ![]() | - |
Parameter | Minimum power On time, MFR self-consumption | Mlt.MinOnPwrTmm | ![]() | Device > Multifunction relay > Self-consumption > Minimum power On time | 0 min to 1440 min | 30 min | 1 | ![]() | - |
Parameter | Minimum On power for MFR battery bank | Mlt.BatCha.Pwr | ![]() | Device > Multifunction relay > Battery bank > Minimum On power | 100 W to 12000 W | 1,500 W | 1 | ![]() | - |
Parameter | Minimum time before reconnection of MFR battery bank | Mlt.BatCha.Tmm | ![]() | Device > Multifunction relay > Battery bank > Minimum time before reconnection | 1 min to 1440 min | 30 min | 1 | ![]() | - |
Parameter | S0 pulses per kWh for feed counter | GM.S0kWhOut | ![]() | AC Side > Measured values > Grid measurements > S0 pulses per infed kWh | 1 to 4294967294 | ‒ | 1 | ![]() | - |
Parameter | Set supplied energy | GM.TotkWhOutSet | ![]() | AC Side > Measured values > Grid measurements > Set total yield | 0 kWh to 4000000 kWh | 0 kWh | 1 | ![]() | - |
Measured value | Grid feed-in counter reading | GM.TotWhOut | ![]() | AC Side > Measured values > Grid measurements > Total yield | ‒ | ‒ | ‒ | ‒ | - |
Measured value | S0-pulses grid feed-in counter | GM.TotS0Out | ![]() | AC Side > Measured values > Grid measurements > S0-pulse feed-in | ‒ | ‒ | ‒ | ‒ | - |
Parameter | Power control module D1: 0 | D2:0 | D3: 0 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 0 | D4: 0 | −1 % to +100 % | 100 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:0 | D3: 0 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 0 | D4: 0 | −1 % to +100 % | 0 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:1 | D3: 0 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 0 | D4: 0 | −1 % to +100 % | 30 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:1 | D3: 0 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 0 | D4: 0 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:0 | D3: 1 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 1 | D4: 0 | −1 % to +100 % | 60 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:0 | D3: 1 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 1 | D4: 0 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:1 | D3: 1 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 1 | D4: 0 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:1 | D3: 1 | D4: 0 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 1 | D4: 0 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:0 | D3: 0 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 0 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:0 | D3: 0 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 0 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:1 | D3: 0 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 0 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:1 | D3: 0 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 0 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:0 | D3: 1 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 0 | D3: 1 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:0 | D3: 1 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 0 | D3: 1 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 0 | D2:1 | D3: 1 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 0 | D2: 1 | D3: 1 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module D1: 1 | D2:1 | D3: 1 | D4: 1 | ‒ | ![]() | Device > Power control module > Active power limitation > D1: 1 | D2: 1 | D3: 1 | D4: 1 | −1 % to +100 % | −1 % | 1 | ![]() | - |
Parameter | Power control module release time | ‒ | ![]() | Device > Power control module > Release time | 0 h to 99 h | 0 h | 1 | ![]() | - |
Parameter | Power control module release value | ‒ | ![]() | Device > Power control module > Release value | −1 % to +100 % | 100 % | 1 | ![]() | - |
Parameter | Power control module fault tolerance time | ‒ | ![]() | Device > Power control module > Error tolerance time | 1 s to 60 s | 5 s | 1 | ![]() | - |
Parameter | Modbus TCP server port | ‒ | ![]() | External Communication > Modbus > TCP server > Port | 1 to 65535 | 502 | 1 | ![]() | - |
Parameter | Modbus UDP server port | ‒ | ![]() | External Communication > Modbus > UDP server > Port | 1 to 65535 | 502 | 1 | ![]() | - |
Parameter | Modbus Unit ID | ‒ | ![]() | External Communication > Modbus > Unit ID | 3 to 123 | 3 | 1 | ![]() | - |